The PERC2 DLL v2.3 model (PERC2_v3x_v2p3.dll, PERCBL with 179 CONs)

The developer reference for src/load_models/perc2_dll/ (model id perc2_dll): what the model is, its record, the values it adds to the PERC1 DLL, how the app fills them from a preset, and what the DLL does that its document does not say. Derived from the PSS/E validation library (not published); results are summarized here and in the user model pages.

What it is

ISO-NE's PERC2 v2.3 is the PERC1 DLL (perc1_dll, PERC1_MODEL.md) with six CONs appended, built for PSS/E 34, 35 and 36 (PERC2_v34_v2p3.dll, PERC2_v35_v2p3.dll, PERC2_v36_v2p3.dll; the app validated the v35 and v36 builds). It is a user load model (USRLOD), not a composite-load component, and it registers the same model name as the PERC1 DLL, PERCBL. Everything the two share behaves identically (79 cases, identical traces outside the voltage reconnect ramps). It is unrelated to PSS/E's built-in PERC2 standard model (PERC2_MODEL.md).

PERC1 DLL (perc1_dll) PERC2 DLL v2.3 (perc2_dll) PERC2 standard (perc2_standard)
PSS/E 34, 35 (DLL) 34, 35, 36 (one DLL per version) 36.7 built in
Record USRLOD 'PERCBL' 12 IT 2 173 33 250 0 USRLOD 'PERCBL' 12 IT 2 179 33 250 0 USRLODC 'PERCBL2U' under MAINxx10
Values 2 ICONs + 173 CONs 2 ICONs + 179 CONs 6 flags + 57 CONs
Stages 4 under, 4 over, 1 frequency each way same momentary + 4-point long tables
Momentary cessation return VLBLK < V < VUBLK, ramp RAMPA VLRCMC < V < VURCMC, ramp RAMPAMC/RAMPUAMC VLrecon < V < VHrecon
Ramp in seconds every ramp CON as given RAMPA, RAMPUA x LFM; the rest as given Tramp x Ldfact
Reactive lead-lag none TAQ/TBQ Taq/Tbq

The record

IBUS 'USRLOD' 'ID' 'PERC**' 12 IT 2 179 33 250 0
 ICON(M) ICON(M+1)
 CON(J) .. CON(J+172)        (the PERC1 DLL's 173, in its row groups)
 TAQ TBQ
 RAMPAMC RAMPUAMC
 VLRCMC VURCMC /

dyr.py writes it with the PERC1 DLL's @! comment rows plus three, the two ICONs on their own line. The document's own DYRE FORMAT says 173 CONs; that record loads silently and breaks momentary cessation, so the app never writes it (validation finding 1.2). The app keeps the two ICONs in the CON dict as integers, FREQ50 (ICON(M)) and MCFLAG (ICON(M+1)), like the PERC2 standard model's flags.

Telling it from a PERC1 DLL record. Both say PERCBL. perc1_dll/dyr.py's parse_perc1_records reads either layout and sets n_con from the header; is_perc1_dll_record / is_perc2_dll_record test it, and both models set the new LoadModel.matches_dyr hook, which find_model_for_dyr checks after the name. A header too broken to read counts as PERC1's, so the error is reported against the older model. .dyr import routes the same way.

The new values

Value Meaning (measured)
FREQ50 (ICON(M)) The document's 50 Hz flag. Ignored: the DLL always measures 60 Hz x (1 + deviation). The app writes 0 and warns on anything else
MCFLAG (ICON(M+1)) 1 = momentary cessation on; any other value is off
TAQ, TBQ Q lead-lag (1 + sTAQ)/(1 + sTBQ). Both 0 bypasses it; TAQ with TBQ = 0 returns NaN
RAMPAMC, RAMPUAMC ramp after a low / high cessation, in seconds (not x LFM)
VLRCMC, VURCMC a ceased load comes back after the filtered voltage has been strictly inside this band for TBLK + TDELY

The defaults are the PERC1 DLL's (perc1_dll's PERC1_DEFAULT_CONS), the four cessation CONs from the vendor sample (1.0, 1.0, 0.9, 1.09), TAQ = TBQ = 0, MCFLAG = FREQ50 = 0, and RAMPA/RAMPUA divided by LFM so a new block ramps over the same seconds as a new PERC1 DLL block.

The cease / reconnect machine

The PERC1 DLL's, as PERC1_MODEL.md "Measured runtime behavior" describes it, with:

  • Ramps. RAMPA and RAMPUA last their CON x LFM (LFM < 0.001 counts as 0.8). RUFRN1, ROFRN1, RAMPAMC and RAMPUAMC last their CON. cons.ramp_seconds() is the one place this rule lives.
  • Momentary cessation (MCFLAG = 1 and FCEASE > 0). The filtered voltage strictly below VLBLK or above VUBLK ceases the load at once (no CMTDELAY): FracOn = 1 - FCEASE. It returns after TBLK + TDELY strictly inside VLRCMC < V < VURCMC (the timer restarts if V leaves), ramping over RAMPAMC/RAMPUAMC to 1 - FCEASE + FRECON x FCEASE - the same partial return as a trip. CMTDELAYC and RAMPA play no part.
  • Stage takeover. The stage timers keep running during a cessation. A stage that trips turns it into an ordinary trip: the load then needs VRPA < V < VRUPA for TDRA (+ CMTDELAYC) and ramps over RAMPA x LFM. With stages at or below VLBLK, a sag longer than the stage delay always ends on the slow path.
  • A new cessation (or trip) during any ramp ceases again from where the ramp had got to.

Ride-through presets (presets.py)

A preset's PERC1 DLL bundle carries over CON for CON (it_bundle / vfd_bundle), with three changes:

  • RAMPA and RAMPUA are divided by LFM, so the preset reconnects over the same seconds as on the PERC1 DLL.
  • VRPA is capped at 0.95 pu (RECONNECT_VOLTAGE_CEILING, the PERC2 standard presets' ceiling). Five presets (ERCOT NOGRR282, PJM, MISO, NERC LLWG, PRC-029) set VRPA = 1.0, which never reconnects after a recovery to 1.0 pu because the window is strict on a voltage that approaches 1.0 from below (the PERC1 DLL preset library's finding 1, and validation finding section 3 on v2.3). preset_gaps(preset) says so for the presets it changes.
  • Momentary cessation stays off; the four new cessation CONs take the vendor sample's values and TAQ = TBQ = 0.

validate_cons

validate_cons(cons, time_step_s, initial_voltage_pu, psse_version=None) returns ConIssue(level, con, message); an empty list means the values mean in PSS/E what they say. Errors are values the DLL turns into nonsense: FCEASE outside [0, 1] and negative FRECON (not clamped: the load exports power or ramps down), negative ramps (FracOn runs below zero), TA or TAQ without TB/TBQ (NaN), IPMAXA <= 0, a stage threshold on the wrong side of the initial voltage, a reconnect window or cessation band that excludes it; with psse_version="36.7", any TA/TB (NaN) and momentary cessation with a reachable VUBLK (the v36 build exits at the end of a high-side cessation ramp). Warnings: ICON(M) set, LFM replaced, cycling (VRPA below a stage, VRUPA above one), IPMAXA < LFM, FRECON < 1 with cessation on (permanent loss per cessation), a stage at or below VLBLK with cessation on (the takeover), FRA/VNOMA not 1, TRA below 2 time steps.

The simulator

simulation.py: with momentary cessation off, the PERC1 DLL simulator on perc1_equivalent(cons) (RAMPA/RAMPUA in seconds, LFM as the DLL uses it, negative delays as 0). With it on, a v2.3 state machine (_run_logic) that adds the two cessation "stages" (zero delay, their own band and ramps), keeps the stage timers running during a cessation, and marks a takeover (escalated in the response); the filters, the power loop and the response shape are the PERC1 DLL simulator's. Checked against PSS/E on every single-dip case of the library (79, 31 with cessation): first cease, first ramp start and ramp length agree within one sample (validation finding 10). Not modelled: the lead-lags and washouts (the app exports them bypassed), the per-run()-call ramp speed-up (a rig effect), Q.

DLL issues the app works around

Issue What the app does
The document's 173-CON format breaks momentary cessation always writes 179
Same model name as the PERC1 DLL routes records by CON count; the report and import label which DLL a record needs
ICON(M) ignored writes 0; warns otherwise
RAMPA/RAMPUA x LFM (the PERC1 DLL does not scale) divides them by LFM in defaults and presets
VRPA 1.0 never reconnects caps preset VRPA at 0.95, reports it in preset_gaps
v36 build: high-side cessation crashes PSS/E 36.7; any TA/TB is NaN validate_cons(..., psse_version="36.7") errors; the app exports TA = TB = 0 and cessation off by default
No range checks in the DLL validate_cons errors before export (build_perc2_dll_dyr_block refuses errors)