The PERC2 standard model (PSS/E 36.7 PERCxx2U)

The developer reference for src/load_models/perc2_standard/ (model id perc2_standard): what the model is, its record, every flag and CON, how the app fills them from a preset, and what PSS/E 36.7.1 does that its data sheet does not say. Derived from the PSS/E validation library (not published); results are summarized here and in the user model pages.

What it is

PERC2 is PSS/E's built-in power-electronic load component (Fortran source percbl2.for, compiled into PSS/E 36.7; no DLL). Like PERC1 standard (PERCxx1U, PERC1_MODEL.md) it is a component of PSS/E's composite load, so it sits under a MAINxx10 record and the composite-load thresholds switch it off (load below 5 MW, |P/Q| below 1.61, load-bus voltage at or below 0.97 pu). Compared with the two PERC1 models:

PERC1 DLL (perc1_dll) PERC1 standard (perc1_standard) PERC2 standard (perc2_standard)
PSS/E 34, 35 (DLL) 36.5+ built in 36.7 built in
Values 173 CONs 30 CONs 6 flags (ICONs) + 57 CONs
Undervoltage cease 4 stages + Option 1 point one point a momentary point + a 4-point long table (3 usable in 36.7.1)
Overvoltage cease 4 stages none a momentary point + a 4-point long table (3 usable)
Frequency cease one point each way, reconnects none one point each way, never reconnects
Reconnect settings per direction one set per cease level: momentary, long low, long high
Reconnect window VRPA < V < VRUPA V > Vrecon VLrecon < V < VHrecon
Ramp CON seconds seconds Tramp x Ldfact seconds
Current limits per axis per axis per axis plus Imax, active current first

The full behavioral comparison is in the PSS/E validation library (not published).

The record

IBUS 'MAINxx10' ID 1 0 0 0 0 0 0 0 0 0  1 0 0 0 0 0 0 0 0 0 /
IBUS 'USRLODC' ID 'PERCxx2U' 230 IT 6 57 8 44 16 CompNum 'CompDesc' <6 flags> <57 CONs> /

xx/IT are the record scope (BL 1, OW 2, ZN 3, AR 4, AL 5 with first field 0). The numbers after IT are NICON (6 flags), NCON (57), NSTATE (8), NVAR (44) and the reserved-ICON count (16). Write them exactly: PSS/E does not check them against the model, a short count makes PERC2 overwrite the next component's memory (a neighbouring PERC1U lost its whole 50 MW at NVAR 40), and a later record with different counts is dropped as "Inconsistent model definitions" (validation finding 2.2). The flags must be integers (1.0 is rejected). dyr.build_perc2_standard_dyr_block writes the flags on the header line and the CONs ten per continuation line, adds an LSTCxx static remainder (fraction -1) for a partial load, and refuses values validate_cons marks as errors.

Flags and CONs

Generated from cons.CON_SPECS (labels, units and notes are the code's own); the default is cons.DEFAULT_CONS.

Slot Name Meaning Unit Default Measured in PSS/E 36.7.1
M+0 VLMflag Momentary low-voltage cease flag 1 1 checks Vtf < VLcease for Tcease; any other value (0, 2, -1) is off.
M+1 VHMflag Momentary high-voltage cease flag 0 1 checks Vtf > VHcease for Tcease. Off still leaves VHcease capping VHrecon.
M+2 VLLflag Long low-voltage cease (4-point table) flag 0 1 checks Vtf < VLCx for TVLCx. PSS/E 36.7.1 times point 3 with TVLC1, not TVLC3.
M+3 VLHflag Long high-voltage cease (4-point table) flag 0 1 checks Vtf > VHCx for TVHCx. PSS/E 36.7.1 times point 3 with TVHC1, not TVHC3.
M+4 FLflag Low-frequency cease (no reconnect) flag 0 1 checks f < FLC1 for TFLC1. The load then does not come back.
M+5 FHflag High-frequency cease (no reconnect) flag 0 1 checks f > FHC1 for TFHC1. The load then does not come back.
J Ldfact Load factor (sets the MVA base) pu 0.8 MVA base = initial P / Ldfact; every pu CON is on that base. <= 0 -> PSS/E uses 0.8 (with a message). The data sheet says > 1 also falls back to 0.8; PSS/E 36.7.1 uses it as given, and the block then cannot draw its own power-flow load if Ldfact > Ipmax.
J+1 QPratio Q/P ratio (initial reactive power) pu 0 Qinit = QPratio x Pinit. The difference to the load's power-flow Q is absorbed as ExtraVars.
J+2 Tt Converter delay s 0.02 PSS/E raises anything below 2 x time step to 2 x time step. The data sheet says it writes a message; 36.7.1 does not.
J+3 Tv Voltage measurement time constant s 0.05 Filters the voltage every voltage check sees. 0 or negative = no filter.
J+4 Tf Frequency measurement time constant s 0.02 Filters the frequency for droop and the frequency cease. Its input is held at 0 deviation while the bus voltage is below 0.7 pu.
J+5 dbfl Droop deadband, lower edge pu freq 0 A frequency deviation (0.005 pu = 0.3 Hz), <= 0.
J+6 dbfh Droop deadband, upper edge pu freq 0 >= 0.
J+7 Kdroop Droop gain pu P / pu f 8 dP = Kdroop x (df - deadband) in pu of the MVA base; P falls when f falls. 0 disables.
J+8 Kvp P-path washout gain pu*s 0 Washout sK/(1+sT) on the bus voltage, added to Pinit. 0 disables.
J+9 Tvp P-path washout time constant s 0.05 Keep > 0 when Kvp != 0.
J+10 Kvq Q-path washout gain pu*s 0 0 disables.
J+11 Tvq Q-path washout time constant s 0.1 Keep > 0 when Kvq != 0.
J+12 Tap P-path lead time constant s 1 Lead-lag (1+sTap)/(1+sTbp) on Pinit + droop + washout.
J+13 Tbp P-path lag time constant s 1 0 bypasses the whole P lead-lag (Tap is then ignored), as in PERC1 standard.
J+14 Taq Q-path lead time constant s 1 Lead-lag (1+sTaq)/(1+sTbq) on Qinit + washout.
J+15 Tbq Q-path lag time constant s 1 0 bypasses the whole Q lead-lag.
J+16 nP P voltage exponent - 0 P = P0 (Vtf/Vinit)^nP in steady state: 0 constant power, 1 current, 2 impedance.
J+17 nQ Q voltage exponent - 0 Same for Q.
J+18 Ipmax Maximum active current pu 1 IpmaxUsed = min(Ipmax, Imax) (the block diagram; the sheet's note 16 says max, PSS/E uses min). Below Ldfact the block cannot draw its power-flow load at 1.0 pu.
J+19 Ipmin Minimum active current pu 0 IpminUsed = max(Ipmin, -Imax). Keep >= 0 or the load backfeeds.
J+20 Iqmax Maximum reactive current pu 0.7 IqmaxUsed = min(Iqmax, sqrt(Imax^2 - Ip^2)): active current has priority.
J+21 Iqmin Minimum reactive current pu -0.7 IqminUsed = max(Iqmin, -sqrt(Imax^2 - Ip^2)).
J+22 Imax Maximum total current pu 1.5 Must be > 0: 0 zeroes the load; a negative value is used as its magnitude.
J+23 fcease Fraction that ceases - 0.9 Outside [0,1] PSS/E clamps it (with a message). 0 turns every cease off.
J+24 VLcease Momentary cease, low voltage pu 0.5 Strictly Vtf < VLcease for Tcease ceases (VLMflag). Above the initial voltage the load ceases at t = 0.
J+25 VHcease Momentary cease, high voltage pu 1.2 Strictly Vtf > VHcease for Tcease ceases (VHMflag). Even with VHMflag off, VHrecon is capped at it: a VHcease below the post-event voltage means the load never reconnects.
J+26 Tcease Momentary cease delay s 0.05 Recovering earlier cancels it; two short dips do not accumulate. Negative acts as 0.
J+27 Tdelay Extra delay before the load is reduced s 0 Tdelay adds to every cease path (momentary, long and frequency) in PSS/E 36.7.1; unlike PERC1 standard, a dip that ends while it runs does not collapse FracOn (PERC1 standard's collapse is followed by NaN, a wrong load or a normal result, intermittently; validation finding 8).
J+28 frecon Fraction of fcease that reconnects - 0.5 Final FracOn = (1 - fcease) + frecon x fcease; > 1 returns above the initial load; negative acts as 0.
J+29 VLrecon Reconnect window, low edge pu 0.6 Reconnection needs VLrecon < Vtf < VHrecon. Raised to VLcease if lower. A long-cease threshold above it lets the load reconnect while still in the sag and cease again (cycling).
J+30 VHrecon Reconnect window, high edge pu 1.1 Lowered to VHcease if higher (whatever VHMflag is).
J+31 Tramp Reconnect ramp (momentary cease) s 1.25 The ramp lasts Tramp x Ldfact seconds (TrampUsed). 0 or negative = instant.
J+32 Trecon Reconnect delay (momentary cease) s 0.05 Time inside the reconnect window before the ramp starts. Negative acts as 0.
J+33 TLrampL Reconnect ramp after a long low-voltage cease s 1.25 Used as TLrampL x Ldfact.
J+34 TLreconL Reconnect delay after a long low-voltage cease s 0.05 0 or negative: the ramp starts the moment the load ceases if Vtf is inside the reconnect window.
J+35 VLC1 Long low-voltage point 1, voltage pu 0.9 Vtf < VLC for TVLC ceases (VLLflag).
J+36 TVLC1 Long low-voltage point 1, time s 2 0 or negative = as soon as Vtf is below the point. Also times point 3.
J+37 VLC2 Long low-voltage point 2, voltage pu 0.8 Vtf < VLC for TVLC ceases (VLLflag).
J+38 TVLC2 Long low-voltage point 2, time s 0.5 0 or negative = as soon as Vtf is below the point.
J+39 VLC3 Long low-voltage point 3, voltage pu 0 PSS/E 36.7.1 ceases after TVLC1 (point 1's time) below this, not after TVLC3.
J+40 TVLC3 Long low-voltage point 3, time s 0 Not used by PSS/E 36.7.1 (point 3 waits TVLC1).
J+41 VLC4 Long low-voltage point 4, voltage pu 0.5 Vtf < VLC for TVLC ceases (VLLflag).
J+42 TVLC4 Long low-voltage point 4, time s 0.15 0 or negative = as soon as Vtf is below the point.
J+43 TLrampH Reconnect ramp after a long high-voltage cease s 1.25 Used as TLrampH x Ldfact.
J+44 TLreconH Reconnect delay after a long high-voltage cease s 0.05 -
J+45 VHC1 Long high-voltage point 1, voltage pu 1.1 Vtf > VHC for TVHC ceases (VLHflag).
J+46 TVHC1 Long high-voltage point 1, time s 1 Also times point 3.
J+47 VHC2 Long high-voltage point 2, voltage pu 1.15 Vtf > VHC for TVHC ceases (VLHflag).
J+48 TVHC2 Long high-voltage point 2, time s 0.5 -
J+49 VHC3 Long high-voltage point 3, voltage pu 99 PSS/E 36.7.1 ceases after TVHC1 (point 1's time) above this, not after TVHC3.
J+50 TVHC3 Long high-voltage point 3, time s 0 Not used by PSS/E 36.7.1 (point 3 waits TVHC1).
J+51 VHC4 Long high-voltage point 4, voltage pu 1.2 Vtf > VHC for TVHC ceases (VLHflag).
J+52 TVHC4 Long high-voltage point 4, time s 0.16 -
J+53 FLC1 Low-frequency cease threshold Hz 58 f < FLC1 for TFLC1 ceases for good (FLflag). At or above the initial frequency the load ceases at t = TFLC1 with no disturbance.
J+54 TFLC1 Low-frequency cease time s 100 -
J+55 FHC1 High-frequency cease threshold Hz 62 f > FHC1 for TFHC1 ceases for good (FHflag).
J+56 TFHC1 High-frequency cease time s 100 -

The defaults

The sheet has no example values. DEFAULT_CONS reproduces PERC1 standard's defaults through the sheet's note-7 recipe (VLMflag only, VLcease = Vcease, Tramp = PERC1 Tramp / Ldfact), so a new PERC2 block behaves like a new PERC1 standard block. VHcease 1.2 / VHrecon 1.1 keep the reconnect window above 1.0 pu, and the long and frequency tables hold a generic table but are switched off. validate_cons(DEFAULT_CONS) is empty; switching VLLflag on with the default VLrecon 0.6 gives the cycling warning, on purpose.

The cease / reconnect machine

simulation.CeaseLogic is this state machine; validation finding 5 has the evidence.

  1. Checks. VLM (Vtf < VLcease for Tcease), VHM (Vtf > VHcease, Tcease), VLL points 1-4 (Vtf < VLCx, TVLCx; point 3 waits TVLC1), VLH points 1-4 (Vtf > VHCx, TVHCx; point 3 waits TVHC1), FL (f < FLC1, TFLC1), FH (f > FHC1, TFHC1). Each has its own timer, started when its condition becomes true and reset when it is not; all comparisons are strict. Vtf is the voltage through Tv; f is PSS/E's bus frequency through Tf, with the input held at nominal while the bus voltage is below 0.7 pu.
  2. Cease. A completed check starts Tdelay; then FracOn = 1 - fcease, and the cease level is the check's: 0 (momentary), 1 (long) or 2 (frequency). The level picks the reconnect delay and ramp: Trecon/Tramp, TLreconL/TLrampL, TLreconH/TLrampH (ramps x Ldfact), or never.
  3. While ceased only checks of a higher level keep timing (escalation: momentary -> long -> frequency).
  4. Reconnect at levels 0 and 1: the timer runs while max(VLrecon, VLcease) < Vtf < min(VHrecon, VHcease) and restarts when Vtf leaves; then FracOn ramps linearly to (1 - fcease) + frecon x fcease. Every check timer restarts at the ramp start, and any check can cease the load again during the ramp.

Ride-through presets (presets.py)

A preset's CONs come from its PERC1 DLL bundle (it_bundle / vfd_bundle), so the three PERC models assume the same facility physics:

PERC2 From the bundle
long low points 1, 2, 4 the distinct undervoltage stages (VDPA/DMA, VDPA1-3/DMA1-3), shallowest first, padded by repeating the last
momentary low (VLMflag, VLcease, Tcease) only for a fourth distinct stage (ERCOT, PRC-029); its reconnect settings equal the long ones
point 3 off: VLC3 = 0, VHC3 = 99 (the PSS/E defect)
long high points 1, 2, 4 the distinct overvoltage stages, reconnecting with TRUPA / RAMPUA
VLrecon max(min(VRPA, 0.95), the highest long-low threshold): above the long points so it cannot cycle, at most 0.95 so a 1.0 pu recovery reconnects
VHrecon, VHcease min(VRUPA, the lowest long-high threshold); VHcease never below it
frequency FUFTP1/TUFTP1, FOFTP1/TOFTP1, flags on; the cease is permanent in PERC2
Trecon, Tramp TDRA, RAMPA / Ldfact (also the long-low pair)
droop, limits, exponents, filters DROOPA x LFM, +-DBA/60, IPMAXA..IQMINA, NPA/NQA, TRA/TVM/TFRQ; Imax = sqrt(Ipmax^2 + Iqmax^2) so it never binds by itself

Every preset passes validate_cons with no issue, and every one (IT and VFD, under- and overvoltage) was exported and run in PSS/E 36.7.1 (app_preset_*). preset_gaps lists the permanent frequency cease and the VRPA ceiling.

validate_cons

Returns error for values that make the record meaningless in PSS/E (Imax 0; Ipmax < Ipmin; a reconnect window that excludes the initial voltage, including VHcease below it with VHMflag off; an active threshold on the wrong side of nominal; FLC1/FHC1 on the wrong side of 60 Hz) and warning for what PSS/E changes silently or what is a hazard (Ldfact outside (0, 1]; min(Ipmax, Imax) < Ldfact; flags other than 0/1; negative timers; Tt < 2 x delt; the VLrecon/VHrecon clamps; an active point 3; a long point above the reconnect window). post_fault_peak_warning is PERC1 standard's, with Imax as a cap.

The simulator

simulation.run_profile(cons, v_of_t, f_of_t, t_end) steps the quarter-cycle grid; simulate_perc2_standard_response and simulate_perc2_standard_frequency_response wrap it for the LoadModel hooks and add trip_events, reconnect_events, cycles, cease_check, cease_level, never_reconnects and stays_tripped_reason. It models the state machine above, the filters and the 0.7 pu gate, the steady-state exponents, the P-priority limits, the Tt lag and droop; not the washout and lead-lag dynamics. Driven by PSS/E's own bus voltage and frequency, it gives PSS/E's cease/reconnect sequence in every comparable library case (tests/test_perc2_standard_simulation.py; the sim section of the library's summary.md). Known difference: in a cycling sag PSS/E re-ceases 4 time steps later per cycle.

PSS/E 36.7.1 issues the app works around

Issue Workaround
Long point 3 is timed by point 1's time presets use points 1, 2, 4; validate_cons warns when point 3 is active
VHcease caps the reconnect window even with VHMflag off VHcease >= VHrecon in defaults and presets; error otherwise
min(Ipmax, Imax) < Ldfact starts the load below its power flow warning
Header counts are not checked the exporter always writes 6 57 8 44 16
Long points above VLrecon cycle in a sustained sag presets raise VLrecon; warning
Vtf must be strictly above VLrecon presets cap VLrecon at 0.95
A 0 pu bus returns NaN as PERC1 standard: noted, not avoidable by CONs