Final report

Date: 2026-11-14 · Plan phase: 12

This report sets the whole project side by side: what was built, how every model did on its task, what was checked against what, where things fail, the verdicts on the hypotheses written before any training, and what would be done differently. The numbers of sections 2 and 3 are gathered by scripts/phase12_report.py into docs/results/phase12/summary.json. Every other number is quoted from the step named beside it, and that step names the script that produces it.

1. What was built

The question throughout: will this machine, at this operating point, on this network, see negative slip at the electrical resonance and feed an oscillation, and how fast will it grow?

Phase What Steps
1 Solver core on the First Benchmark Model: steady state, linearisation, modes, time integration 01
2 Induction generator, then the doubly-fed plant with its full controls on radial and meshed networks, in two formulations and a second time-domain code 02 to 07
3 Datasets: T1 (growth rate, 12 parameters, 131,072 cases), T2 (response in time, 4 parameters, 32,768 trajectories), a generic converter, protection 08, 15 to 17, 33, 35
4 First learned models on T1, feature studies, uncertainty 09 to 11
5 Physics-informed networks: a forward one, and the eigenvalue residual as a loss 12, 13
— Deterministic screens: how little information decides stability, for both plant types, with noise, uncertain network data, outages, several plants, delay and shunt capacitance 14, 17 to 32
6 Where the physics goes: features, baseline, loss, architecture, on T1 and T2 34, 36, 37
7 Operators and sequence models on T2 38
8 From a measured current back to the mode and the parameters 39
9 Outside the training range, and when to call the solver 40
10 Design search for damping 41
11 Model registry, screening service, model card 42

The screening work between Phases 5 and 6 was not in the plan. It grew out of step 14 and became the larger half of the project.

2. The findings that matter

  1. The mechanism is what the plan said it was, and a hand calculation carries most of it. A doubly-fed plant's current controller acts as rotor resistance; at the network resonance the slip is negative and so is the machine's resistance. The root of the loop impedance of network, machine and current loop is within 1.3 1/s of the full solver on average (step 08).
  2. A positive-sequence stability model cannot see the problem at all. It reports every unstable case as stable (steps 06, 14). It is exact for the slow mode below 2 Hz and blind above (step 21).
  3. The safest screen is deterministic and needs no training data. A 2 × 2 admittance scan of the plant at about a hundred frequencies, a least-squares fit, and the fitted plant closed on the network at the 32 ends of the ranges of its data. With a scan good to 1 % and a network known to within 10 % it clears no unstable case in 24,659 and clears 58 % of doubly-fed cases and 71 % to 88 % of converters (step 24). It holds with outages (25, 26), several plants on a bus (27, 32), control delay (29) and shunt capacitance (30).
  4. A learned screen is cheaper and narrower. Inside its training range, the hand calculation plus a learned correction, as an ensemble of five, needs the solver for 0.7 % of cases and calls no unstable case stable (step 40). Outside the range no detector makes it safe.
  5. Physics belongs in the inputs or the baseline, not in the loss. A physics penalty in training was the worst use of the physics on both tasks, at five to eight times the cost (step 37).
  6. Architecture matters less than inputs. No operator or sequence model beat a plain perceptron that is given the reduced model's response (step 38).
  7. From a measurement, the series compensation can be read and the phase-locked loop cannot (step 39).
  8. There is no limit cycle. An unstable case grows until the plant trips; protection decides how it ends and not whether (step 33).

3. Every model on its task

Every model on its task

T1: growth rate of the sub-synchronous mode from 12 parameters

Mean absolute error in 1/s. Trained on 100,000 cases unless stated.

Model In distribution Boundary High compensation Low speed Fast current loop Weak parallel path Other machine
Hand calculation (no training) 1.27 1.98 2.01 2.81 1.90 1.98 1.26
Trees, N 0.301 0.477 1.47 0.875 2.64 0.889 0.433
Trees, F 0.127 0.176 0.557 0.627 0.570 0.245 0.139
Trees, R 0.158 0.182 0.559 0.838 0.499 0.252 0.161
Perceptron, N: no physics 0.101 0.162 0.414 0.433 0.545 0.358 0.136
Perceptron, F: physics as features 0.098 0.129 0.390 0.400 0.374 0.222 0.116
Perceptron, R: physics as baseline 0.078 0.064 0.250 0.315 0.199 0.175 0.075
Perceptron, L: physics as penalty 0.129
Perceptron, F and penalty 0.120
Ensemble of five, N 0.090 0.148 0.378 0.392 0.532 0.342 0.114
Ensemble of five, F 0.090 0.119 0.376 0.375 0.361 0.202 0.104
Ensemble of five, R 0.071 0.059 0.246 0.272 0.183 0.166 0.066
Gaussian process, N, 1,000 cases 0.197
Gaussian process, F, 1,000 cases 0.113
Gaussian process, R, 1,000 cases 0.268

Single perceptrons and trees are means of five seeds (step 34); the ensembles are one each (step 40); the Gaussian processes are means of three seeds (step 11). The outside sets of the penalty arms are in step 34.

  • The baseline wins. The correction to the hand calculation is the best form in distribution and on every outside set, as one network or as five.
  • Trees are no match for a perceptron here unless they are given the hand calculation, and then they are within 30 % of it.
  • A Gaussian process at 1,000 cases is as good as a perceptron at 1,000 (0.20 against 0.21 1/s, steps 11 and 34) and cannot be trained on more.
  • The penalty arms are worse than no physics.
  • Speed: the solver takes 10 ms a case and the hand calculation 1.7 ms. A perceptron takes 1.4 µs a case in a batch and 0.2 ms alone (step 11).

T2: the response over 0.3 s from 4 parameters

Median relative error of the response, models trained on 25,000 trajectories (step 38). The reduced model alone is at 0.61 in distribution.

Model In distribution High compensation Low speed Fast current loop Training (s)
Perceptron, no physics 0.036 0.345 0.109 0.189 83
Perceptron, reduced response as inputs 0.008 0.023 0.046 0.058 92
DeepONet, with inputs 0.036 1.035 0.122 0.287 47
Fourier neural operator, with inputs 0.011 0.242 0.057 0.136 84
Temporal convolutional network, with inputs 0.012 0.059 0.048 0.073 83
Transformer, with inputs 0.025 0.076 0.079 0.118 198
Arm A: linear system with learned matrices 0.025 0.047 0.053 0.127 237
  • The reduced model as inputs is worth more than any architecture. It cuts the error of every architecture by 29 % to 77 %.
  • Only the perceptron with those inputs stays under 10 % error over the whole window on all three outside sets.

T3: the mode from 0.3 s of phase current

Median error of the growth rate in 1/s (step 39).

Method 40 dB 20 dB 0 dB
Matrix pencil, fault recorder 0.047 0.42 1.99
Prony, fault recorder 2.36 2.56 14.8
Matrix pencil, phasors at 120 /s 0.11 0.74 1.95
Phasors at 60 /s 0.57 1.39 2.16
Phasors at 30 /s 2.14 2.28 4.07
Convolutional network, fault recorder 0.057 0.12 0.42
  • Matrix pencil on a clean record, a trained network on a noisy one. They cross near 40 dB.
  • Of the plant's parameters, the waveform is 12 to 190 times more sensitive to the series compensation than to any other. The phase-locked loop is lost once the noise passes about 20 dB.

The screen with a fallback

Share of in-distribution test cases sent to the solver under a rule that called no unstable case stable on validation (step 40).

Screen Sent to the solver Unstable called stable, of 1,376
Hand calculation with a margin 68.8 % 0
Perceptrons, no physics, margin only 14.8 % 0
Perceptrons, no physics, with ensemble spread 4.3 % 0
Baseline arm, margin only 3.0 % 0
Baseline arm, with ensemble spread 0.7 % 0

Outside the training range the last row calls 16 of 1,476 unstable cases stable at high compensation and 8 of 920 at low speed. The hand calculation with its margin calls none stable on any set, at 64 % to 81 % of cases sent to the solver. Cheap and narrow against dear and wide: the service of step 42 uses the first inside the range and the solver outside.

Design search

Worst-case growth rate over 12 scenarios, with all five capacitor segments in service (step 41). The best design found is at +0.49 1/s.

Method Score at the end (1/s) Solver calls to within 1 1/s of the best
Random search +2.76 ± 0.55 never in 2,880
CMA-ES +0.52 ± 0.05 408 to 1,308
Bayesian optimisation +0.50 ± 0.03 216 to 312
Surrogate, 20,000 training calls, solver-confirmed +2.76 ± 0.72 never
  • The surrogate promised −0.7 1/s and the solver found +2.8. Its average error on fresh cases was 0.05 1/s.
  • A damping controller is worth 3 to 11 1/s and lets four of five segments stay in service (−4.5 1/s). The nonlinear model agrees with the eigenvalues to 0.16 1/s.

The service

t1-screen 1.0.0 (step 42, card in docs/model_cards/t1-screen.md): growth-rate error 0.069 1/s in distribution, 0.9 % of cases to the solver, 0 of 1,376 unstable cases called stable. Through the service, 500 test cases all came back with the right sign; an answer from the model takes 3.2 ms and one from the solver 15 ms.

4. Validation record

The full record is docs/VALIDATION.md. In short:

Rung Status
1. Hand calculations Done. The slip estimate matches the benchmark's locked-shaft mode within 2.6 %; the induction generator's self-excitation boundary within 0.9 points of compensation; the doubly-fed plant's largest stable gain within 1.9 % at standard tuning
2. Internal consistency Done. Steady states to 1e-13; time-domain growth against eigenvalue to 1e-7 1/s on every system; RK4 of order 4.00; CPU against GPU to 1e-11
3. Published results Partly. Torsional frequencies of the First Benchmark Model within 0.005 Hz. One published doubly-fed case (step 43), with its unstated current-loop gain fitted: frequency within 1.7 Hz, compensation boundary within 2 points, the gain boundary off by about a third. Open: the benchmark's generator data against the 1977 tables, and a doubly-fed case with all its gains published
4. Independent formulation Done for the current-loop model: polynomial roots of the loop impedance against state-space modes to 2e-8; a second time-domain code in phase coordinates to 0.00014 1/s. Three more routes to the modes agree: the Nyquist count on scans (step 18), a rational fit (19), a fitted plant closed on the network (20). A second implementation of the full controls in phase coordinates agrees to 5e-8 of the response (step 44). Open: an electromagnetic-transient tool
5. Recorded events Open. No recorded waveform was compared. Step 39 ran on simulated records

What the learned models were checked against is the solver, on test folds they never saw and on sets outside the training range. The solver is checked as above. No number in this repository has been compared with a measurement on a real plant.

5. Failure catalogue

Where each thing fails, how it shows, and what catches it.

What Where it fails Seen how What catches it Step
Positive-sequence dynamic model Every sub-synchronous case: all unstable cases reported stable No warning of any kind Nothing in the model. Use it only below 2 Hz 06, 14, 21
Hand formula for the resonance Near the boundary the sign is right half the time; blind to the slow mode of the outer loops (478 unstable cases cleared) Silent A margin of 1 to 5 1/s; the phasor-domain model for the slow mode 08, 14, 18, 21
Hand calculation without voltage feed-forward Up to 32 points of compensation pessimistic On the safe side 04
Loop-gain (passivity) screen Series resonance: clears 0.2 % of doubly-fed cases; with a control delay clears a third of what it did Safe, and useless there The guarded gain margin or the Nyquist count 18, 29
Pointwise tests on a thin scan Clears unstable cases when points are more than 2.5 % apart Silent A fit, or a finer scan 18, 19
Rational fit through the points Any noise: one part in a million flags most stable cases Loud The least-squares fit 19, 20
A margin in 1/s for wrong network data 10 % error needs 10 1/s and clears almost nothing Loud Evaluate at the ends of the ranges 22, 23
A margin on the intact network One case in ten at −10 1/s is insecure after losing the parallel path Silent Screen each outage 25
One scan reused across outages or loadings, converter 203 and 465 insecure cases cleared; wrong verdict in 7 % to 17 % of loadings Silent Two or three scans and interpolation at the operating point 25, 26, 31
Judging converters on a bus one at a time Misses 6 % to 25 % of unstable pairs Silent Scan each at the joint operating point and add 27
Network model without shunt capacitance Misses 75 % to 85 % of the unstable cases above 58 Hz Silent Include it, at both ends of its range 30
A stride through a Sobol dataset as a sample Biased subset; four steps had to be rerun Silent A random subset 29
Learned model as a screen, no margin Calls 21.7 % of near-boundary unstable cases stable Silent Margin set on validation; then the rule of step 40 09, 34, 40
Learned model outside its range Error doubles within 0.06 of a range in compensation or speed; unstable cases cleared Spread rises in 29 % to 58 % of cases, not enough A range check on the inputs 40
Arm R with a wrong baseline Hand calculation off by 1 1/s gives a model off by 0.85 1/s; on T2 worse than no physics at high compensation Silent Arm F, which learns to discount the feature 10, 36
Physics penalty in the loss Worse than no physics from 1,000 labels on, at any weight Loud (validation error) Do not use it 13, 34, 36
Label-free eigenvalue residual Finds an eigenvalue, the wrong one Loud Labels 13
Forward PINN on a long window Settles on the steady state, which satisfies the equations Loud Scale each state; march in short windows 12
Arm A at the shared learning rate Loss overflows; a non-finite loss into the backward pass of the matrix exponential on the GPU never returns A run that hangs for 8 hours A quarter of the rate; skip non-finite steps; a watchdog on every run 36
Operators and sequence models without physics inputs High compensation: errors of 0.67 to 1.32 of the response Silent The reduced response as inputs 38
Prony on a short record 2 1/s off with no noise Silent Matrix pencil 39
Matrix pencil in noise Breaks between 20 and 10 dB Silent A trained network 39
Phasor unit at 60 or 30 frames per second Frequency folded, 8 Hz and 30 Hz off Silent Unfold with a second source, or a recorder 39
Parameter fit through the model from a poor start Converges to the wrong minimum in over 90 % of cases Misfit stays above the noise Start from a network's answer 39
Ensemble spread or conformal interval outside the range Covers 36 % to 94 %, not 90 % Silent The range check 11, 40

6. Verdicts

The five hypotheses (step 37)

Hypothesis, written before training Verdict
1 With little data, F and R beat N by a wide margin Holds for F on both tasks. For R only at 100 cases on T1, and only from 1,000 on T2
2 F and R degrade where the hand calculation is invalid, R more than F Rejected on T1, where R degrades least. Holds for R on T2. It turns on how wrong the physics is
3 L extrapolates better than N, at several times the cost Rejected on both tasks. The cost is five to eight times
4 L is harder to make work on the time-domain task Holds
5 With abundant data the arms converge in distribution Half right on T1; rejected on T2

The plan's targets

Target Result
No missed unstable case in distribution with the solver called on under 10 % of cases (Phase 9) Met: 0 of 1,376 at 0.7 %
A table and a figure per task from which an arm can be chosen (Phase 6) Met (step 37)
The horizon beyond which each model should not be trusted (Phase 7) Met within the 0.3 s window; no rollout beyond it
A list of parameters that cannot be identified (Phase 8) Met on simulated records
Table of best design, solver calls and wall time per method (Phase 10) Met (step 41)
Fresh clone, uv sync, one command starts the service and the suite passes (Phase 11) Met, with a smaller model on a fresh clone: weights and datasets are not committed (step 42)
Validation against recorded events (rung 5) Not met

7. What would be done differently

  1. Start with the screens. The plan put learned models at the centre and treated the impedance scan as a cross-check. Step 14 showed that the question an engineer asks, whether a case can be cleared without a full study, is answered better by a deterministic test with a stated margin than by a model with a small average error. Sixteen steps followed from that. They should have been the plan.
  2. Judge every screen by its tail from the first day. Mean error ranked the models one way and the count of unstable cases cleared ranked them another (step 14). The count is the one that matters.
  3. Fix the training length before comparing data budgets. On T2 no arm improved from 1,000 to 25,000 trajectories at 4,000 steps, and four times the steps cut the error by 63 % to 75 % (step 36). Budgets were being compared at a length that hid them.
  4. Take random subsets of quasi-random datasets. A stride through a Sobol set is a corner of it (step 29). Four steps had to be rerun.
  5. Put a watchdog beside every long run from the start. One hung run cost 8 hours (step 36).
  6. Write the inverse problem's data first. Phase 8 was planned around recorded waveforms that were never obtained. The measurement models and the bound could have been built in Phase 3, next to the datasets, and would have told earlier which parameters are worth carrying as unknowns.
  7. Tie the plant to a published one. Every absolute number here belongs to a plant assembled from representative values. The method transfers; the limits do not (docs/VALIDATION.md, last section).
  8. Drop the penalty arms sooner. Step 13 already showed the state matrix costs 96 % of a solve. Steps 34 and 36 confirmed at length what that implied.

8. Not done

Phase 13 (steps 43 to 52) took up every item below; the notes say what came of each. The two screening recommendations are summarised in docs/SCREENING.md.

  • Rungs 3 and 5 of the validation ladder in part or whole: published eigenvalue tables for a doubly-fed plant, and recorded events. Phase 13 takes these up; rung 3 is partly met (step 43), rung 5 stays open.
  • A second implementation of the full controls, or a comparison with an electromagnetic-transient tool. The second implementation is done (step 44); the EMT comparison stays open.
  • An inverse PINN and a parametric PINN (Phase 5 built the forward form and the eigenvalue residual). Done (step 47): the parametric PINN settles on the steady state (error 0.99); the inverse PINN does not improve on its start and loses the PLL bandwidth, where Gauss-Newton through the solver reaches the bound.
  • A neural ODE with a nonlinear correction for arm A. Done (step 46): 11 % to 34 % less error than arm A, still more than twice the error of the perceptron with physics inputs in distribution.
  • Three disturbances on T2; the dataset has one. Done (step 45): with the reduced model's response as inputs, error 2.6 to 3.5 times lower in distribution and 6 to 13 times lower at high compensation for a compensation step and a voltage dip; no gain for a power ramp, which the reduced model does not see.
  • The out-of-distribution study on T2, and a physics-residual detector. Done (step 48): neither residual beats the ensemble spread on T1; on T2 arm F's error grows slowly outside the range and its spread flags every response with more than 10 % error.
  • The stretch goals: System C in full as a learned task (done, step 49: the learned screen with the scan as inputs clears 80 % in distribution with none missed, and does not beat the deterministic scan screen), a network of many plants with a graph network (done, step 51: trained on 2 to 4 buses, it halves the error of a plant-by-plant study up to 8 buses; a fixed-size perceptron does not extrapolate), active learning (done, step 50: labelling by the sign's uncertainty brings the screen to 0.89 % of cases to the solver with 4,000 labels, against 7.2 % at random, but misses 2 unstable cases in one of three repeats).