PERC2 v2.3 is ISO New England's second user-defined model (PERC2_v34, v35 and v36 builds
of PERC2_v3x_v2p3.dll). It turns out to be the PERC1 DLL with six CONs appended: a
reactive-power lead-lag (TAQ, TBQ) and momentary cessation's own reconnect band and ramps
(VLRCMC, VURCMC, RAMPAMC, RAMPUAMC). See the model overview for
how it compares with the others and the model reference for how the
app writes it.
| PSS/E versions validated | 35.6.4 with PERC2_v35_v2p3.dll and 36.7.1 with PERC2_v36_v2p3.dll, one plan on both |
| Needs | the DLL for your PSS/E version, loaded as a user-defined model |
| Record | USRLOD 'PERCBL' 12 IT 2 179 33 250 0, two ICONs, then 179 CONs |
| PSS/E runs | 285 cases on 35.6.4 (89 of them on the PERC1 DLL, for comparison) and 194 on 36.7.1 |
| Automatic checks | 351 of 351 pass |
| Reference | the vendor document and its sample record |
The PSS/E runs behind these counts are in the authors' PSS/E validation library, which is not published.
One 285-case plan ran on both builds: the record, every documented CON on its own, ramps against the load factor, momentary cessation, out-of-range values, a one-machine network, the records the app exports, and the same scenarios on the PERC1 DLL. The app's simulator was then compared with PSS/E on all 79 single-dip cases, 31 of them with momentary cessation: it reproduces PSS/E's first cease, ramp start and ramp length within one sample.
| Question | Answer |
|---|---|
| What is v2.3? | The PERC1 DLL plus six CONs. Every PERC1 DLL behavior holds on it, and the 79 cases that use no v2.3-only CON give the PERC1 DLL's exact trace outside the voltage-reconnect ramps. |
| Does the document's record work? | Its record format (173 CONs) loads without a message but is wrong: a load that ceases never comes back. The vendor sample's header (179) is right. |
| Does the DLL do what the document says? | Mostly. Eight statements are contradicted (below). |
| Defects | The v36 build stops PSS/E 36.7 when a high-voltage momentary cessation ramp ends, and returns not-a-number for any non-zero TA or TB. The v35 build does neither. |
| Is v36 otherwise the same? | Yes. Outside those two defects the builds agree within 0.001 on V, P, Q and FracOn on every case. |
| Document | PSS/E |
|---|---|
| The record has 173 CONs | 179. 173 loads silently and breaks momentary cessation |
ICON(M) = 1 means 50 Hz |
Ignored. The DLL always measures frequency against 60 Hz |
TA/TB are bypassed by setting them to 0 |
TA with TB = 0 returns not-a-number: both must be 0. On v36, any non-zero value does |
RAMPA is multiplied by the load factor |
Right, and so is RAMPUA, which is not documented |
TBLK waits for the voltage between VLBLK and VUBLK |
It waits for VLRCMC < V < VURCMC |
The ramp after a cessation is RAMPA or RAMPUA |
It is RAMPAMC or RAMPUAMC |
| Option 2 uses CONs J+160 to J+163 | Also FCEASE, FRECON and the stage trips, which take it over |
| The reactive lead-lag is J+166 and J+167 | Those are the reactive washout. The lead-lag is J+173 and J+174 |
The header's CON count is the only thing that tells the two DLLs' records apart, which is how the app routes them. A record with no ICON line switches momentary cessation on from unset memory. With no DLL loaded, PSS/E prints a "not accessible" message once and then simulates the load as zero.
RAMPA and RAMPUA are stretched by the load factor (LFM): a 2 s ramp is 1.6 s at
LFM 0.8. RUFRN1, ROFRN1, RAMPAMC and RAMPUAMC are not. A PERC1 DLL record moved
to v2.3 unchanged therefore reconnects its voltage ramps 1.25 times faster at the usual
LFM of 0.8. The app divides both ramps by LFM so a preset keeps its seconds.
The load ceases at once when the filtered voltage is strictly below VLBLK (or above
VUBLK), with no delay, and returns after the voltage has been inside VLRCMC to VURCMC
for TBLK + TDELY. It ramps over RAMPAMC (or RAMPUAMC) to 1 - FCEASE + FRECON × FCEASE, so with FRECON below 1 every cessation loses part of the load for good.
The stage timers keep running during a cessation. A stage that trips takes the cessation
over: the load then waits for the stage's reconnect window and TDRA. The vendor's sample
with momentary cessation on comes back after about 10 s, not the 0.05 s the cessation's own
settings suggest.
After a cessation the PERC1 DLL returns once the voltage is above VLBLK; v2.3 waits for
VLRCMC. A recovery to 0.79 pu reconnects on one and stays ceased on the other.
At the end of every high-voltage momentary-cessation ramp the v36 build stops the whole PSS/E 36.7 process (Fortran runtime error, exit code 66). A study loses every result of the run, not just this load, and the error appears only on the console. The low-voltage side never crashes.
On the v36 build any non-zero TA or TB returns not-a-number from the first time step. The
reactive lead-lag (TAQ/TBQ) works on both builds when TBQ is above 0.
In a 50 Hz case the DLL trips on over-frequency with no disturbance, with ICON(M) at 0 or
- It cannot be used in a 50 Hz system unless its frequency settings are written for 60 Hz × (f / 50).
Only LFM below 0.001 is replaced (by 0.8). A FCEASE above 1 makes the load export power; a
negative FCEASE makes a trip raise the load to 150 %; a negative ramp runs FracOn below
zero and never stops; a reconnect window that excludes 1.0 pu never reconnects. None of these
produces a message.
- Records are written with the 179-CON header and routed on import by the header's CON count (173 reads as the PERC1 DLL, 179 as this model).
- Presets carry over from the PERC1 DLL's bundles CON for CON, with
RAMPAandRAMPUAdivided byLFM,VRPAcapped at 0.95 pu (the five presets with 1.0 would never reconnect), momentary cessation off, and the four new cessation CONs at the vendor sample's values. - The editor flags every hazard above: out-of-range
FCEASE,FRECONand ramps;TA/TBandTAQ/TBQthat return not-a-number, and anyTA/TBfor PSS/E 36.7;ICON(M)set; the high-voltage crash with momentary cessation on; the permanent partial loss and the stage takeover; reconnect windows that exclude 1.0 pu; and cycling.
- The two builds were run on one PSS/E version each (35.6.4 and 36.7.1). The PSS/E 34 build was not run.
- Dips to exactly 0 pu are excluded from the simulator comparison, because the test setup swells the bus to about 1.7 pu for 0.1 s after them.
- Out-of-range behavior was measured at the values listed, not swept.
- Results are for the builds tested; a later build of either DLL may behave differently.